![]() |
|
|
|
|
||
|
Volume 9 Issue 1
|
June 2006
|
![]() |
|
What are the power requirements for T8 fluorescent lamps?It may be expected that the electric power needed to operate a 32-watt T8 fluorescent lamp will be 32 watts; however, this designation is simply the nominal power of the lamp. The relevant American National Standards Institute (ANSI) document states that the rated lamp power is 32.5 watts under standard test conditions (ANSI C78.81-2005). ANSI further indicates that average lamp power shall not exceed 34.6 watts, which is 6.5% above the rated value. Since this upper limit applies to the average value of the power needed to operate 32-watt lamps, it is possible for individual lamps to exceed 34.6 watts. Since specifiers may select lamps based on efficacy, the variation in lamp power could make calculations of lamp efficacy more difficult without knowledge of the actual power and the associated uncertainty for a specific lamp model. ANSI considers the 4-foot, 32-watt T8 lamp to be a rapid-start lamp, but it is commonly operated using an instant-start circuit in which the two pins on each end of the lamp are electrically connected or shunted together. Lamps operated on instant-start circuits have lower power than those operated on rapid-start circuits because there is no electrode heating with instant-start operation. However, the difference in lamp power between instant-start and rapid-start operation is not equal to the electrode heating power because the lamp discharge efficiency is lower for instant-start operation. NLPIP investigated lamp power differences among lamp models. NLPIP selected lamps designated as 32-watt lamps, operated them on a low-frequency reference ballast per ANSI standard C82.3-2002, and measured the electric power needed to operate the lamps. The lamps had correlated color temperatures (CCT) of 3500 K and 4100 K, which are the most common CCTs sold. Three samples of each lamp model were measured. Figure 3 shows the measured power values. The horizontal axis shows the description of each lamp model tested from manufacturers A, B, and C. Error bars show the combined uncertainty of the measured values for each lamp model. All measured lamp power values were higher than the ANSI-rated power of 32.5 watts. Five of the lamp models exceeded 33.5 watts, which is 3% above the ANSI-rated value. However, this is within the tolerance described in the ANSI standard (lamp power not to exceed 5% plus 0.5 watts). Specifiers should consider the fact that lamp power can exceed the expected value of 32 watts by more than 5% in any estimation of operating costs.
In most cases, the measured electric power values for the RE80 HLO, LL lamps were higher than the values for the RE80 lamps, by as much as 1.2 watts. In Question: What is the light output of T8 fluorescent lamps?, NLPIP showed that the light output of the RE80 HLO, LL lamps averaged 8% higher than the RE80 lamps. Therefore, replacing RE80 lamps with RE80 HLO, LL lamps with no change in luminaire layout or ballast factor will result in more light output and higher power. Customers who are mostly interested in energy savings should change to a lower ballast factor or change their luminaire layout by using fewer luminaires. Today, T8 fluorescent lamps are commonly used with high-frequency electronic ballasts. High-frequency operation of fluorescent lamps reduces lamp power for the same light output (Campbell et al. 1953). As stated in the ANSI standard (ANSI C78.81-2005), the lamp power for high-frequency operation is approximately 6% lower than for low-frequency operation, when the lamp is operated as an instant-start lamp. Nevertheless, unknowingly operating a lamp with higher-than-nominal power on a high-frequency electronic ballast will result in an increase in the lighting system's connected load, leading to higher operating costs than expected. For example, the reported input power for a typical two-lamp, high-frequency electronic ballast with a normal ballast factor (0.88) is 58 watts. However, the ballast input power will increase by 3-4% for lamps with 5% higher power than expected (as measured on a low-frequency reference ballast). Specifiers should include the variation in connected load in estimations of operating costs. |
||||
|
||||
|
||||